Burst Sensor
Burst detection sensor


Installed on the upper part of the Rupture Disc Holder, it maintains a Normal On signal. When the pressure inside the tank or piping exceeds the specified limit and the rupture disc bursts, the sensor film breaks, causing the signal to switch Off. This allows separate monitoring devices or DCS equipment to detect the rupture. It is a burst detection sensor for rupture discs.
Sensor type |
Burst Sensor (Installed on the upper part of Rupture Disk Holder) |
|---|---|
Operation |
Maintains Normal On state → When rupture disk bursts, sensor film breaks → Signal Off occurs |
Application |
When pressure inside tank or piping exceeds specified limit |
Output Function |
Signal can be recognized by separate monitoring device or DCS |
Features |
Manufactured as ‘integrated type’ or ‘separated type’ depending on rupture disc model |
|
Electrical Specifications (Including 1.5m extension cable) |
Ui: 25.5 V Ii: 90 mA Pi: 0.63 W Ci: 0.01 nF Li: 1.66 μH |


A Burst Sensor integrated with the rupture disc. While attached to the rupture disc, it maintains a Normal On signal. When the pressure inside the tank or piping exceeds the specified limit and the rupture disc bursts, the sensor film breaks, causing the signal to switch Off. This allows separate monitoring devices or DCS equipment to detect the rupture. It is a burst detection sensor for rupture discs.
Sensor type |
Burst Sensor (Integrated with Rupture Disk) |
|---|---|
Operation |
Maintains Normal On state → When rupture disk bursts, sensor film breaks → Signal Off occurs |
Application |
When pressure inside tank or piping exceeds specified limit |
Output Function |
Signal can be recognized by separate monitoring device or DCS |
|
Electrical Specifications (Including 1.5m extension cable) |
Ui: 25.5 V Ii: 90 mA Pi: 0.63 W Ci: 0.01 nF Li: 1.66 μH |


A cable-type Burst Sensor integrated with the rupture disc. Installed while attached to the rupture disc, it maintains a Normal On signal. When the pressure inside the tank or piping exceeds the specified limit and the rupture disc bursts, any designated break point in the cable disconnects, causing the signal to switch Off. This allows separate monitoring devices or DCS equipment to detect the rupture. It is a burst detection sensor for rupture discs.
Sensor type |
Cable-type Burst Sensor (Integrated with Rupture Disc) |
|---|---|
Operation |
Maintains Normal On state → When rupture disc bursts, cable break point disconnects → Signal Off occurs |
Application |
When pressure inside tank or piping exceeds specified limit |
Output Function |
Signal can be recognized by separate monitoring device or DCS |
|
Electrical Specifications (Including 1.5m extension cable) |
Ui: 25.5 V Ii: 90 mA Pi: 0.63 W Ci: 0.02 nF Li: 1.24 μH |